What is the _ instrument explosion-proof thermocouple installation requirements
by:JVTIA2020-10-29
Explosion-proof thermocouple installation requirements 1, in order to make the measurement end of the thermocouple, and had good heat exchange between the measured medium, should be a reasonable choice of observation, try to avoid the valve, elbow and thermocouple pipeline and equipment near the corner of installations.
2, with a thermocouple with heat transfer and heat loss protection casing, in order to reduce the measurement error, thermocouple and thermocouple should have enough: (insert depth
1)
For the measurement of pipeline fluid temperature thermocouple, generally should be measuring end is inserted into the pipe (
Vertical or inclined installation)
。
As the current body of pipe diameter is 200 mm, the thermocouple insertion depth should choose 100 mm.
(
2)
For high temperature and high pressure and high velocity of temperature measurement,
Such as main steam temperature)
, in order to reduce cases of fluid resistance and prevent cases break under the action of a fluid, can take protecting tube shallow inserted way or use hot thermocouple.
Shallow inserted type thermocouple protection tube, its depth into the steam pipe should be no less than 75 mm;
Heat sets the standard of thermocouple insertion depth is 100 mm.
(
3)
If is need to measure the temperature of flue gas, although the flue is 4 m in diameter, thermocouple insertion depth of 1 m.
(
4)
When measuring the original insertion depth of more than 1 m, shall be installed vertically, as far as possible or add racks and protect casing.