This is a lot of people will encounter problem, k type thermocouple temperature measurement uncertainty often, but there is a problem you should find the problem first.
1。 Improperly installed into the error of the
thermocouples should not be in too close to the door and heating, the depth of the insert should be at least 8 ~ 10 times the diameter of the protecting tube, the location of the installation and insertion depth cannot reflect the reality of the furnace temperature. Thermocouple protection tube and the wall between the interval of missing thermal insulation material, overflow or cold air into the furnace heating, so the space between the thermocouple protection tube and furnace wall hole used refractory mortar or insulating material such as asbestos rope jam, in order to avoid cold and hot air convection and affect the accuracy of temperature measurement. The installation of thermocouples should as far as possible to avoid the strong magnetic field and strong electric field, should not be thermocouple and the power cable line in the same catheter in order to avoid interference caused by errors. Thermocouple cannot be installed in a few measured medium flowing area, when measured with thermocouple tube gas temperature, thermocouple must be made against the flow direction of installation, and fully contact with the gas.
2。 Error of the insulation deterioration and the introduction of the
such as thermocouple protection tube and anchor plate too much dirt or salt slag between the thermocouple interelectrode and wall insulation fault, at high temperatures is more serious, which not only causes the thermoelectric potential loss but also can introduce interference, the resulting error sometimes can reach on baidu.
3。 Thermal inertia is introduced into the error of the
because of thermocouple thermal inertia instrument behind the change of the measured temperature, indicating value of this influence is particularly acute in rapid measurement. So should be used as thermal electrode is small, small thermocouple protection tube diameter. Temperature measuring environmental permits, even protecting tube can be taken. Due to measurement lag, using thermocouples detect temperature fluctuations of the amplitude of the furnace temperature fluctuation amplitude of the small. Measurement lags behind, the greater the fluctuation amplitude of the thermocouple is smaller, and the actual temperature difference. When using the time constant of thermocouple temperature or temperature control, instrument display temperature fluctuation is small, but the actual furnace temperature fluctuations can be quite large. In order to accurately measure temperature, should choose small thermocouple time constant. With thermocouple time constant is inversely proportional to the heat transfer coefficient, heat the density and specific heat is proportional to the diameter, material, such as to reduce the time constant, in addition to the increased heat transfer coefficient, the most effective way is to try to decrease the size of the hot end. Use, usually USES the material with good thermal conductivity, thin, small diameter of the tube wall to protect casing. In the precision of temperature measurement, using unprotected casing bare wire thermocouple, thermocouple easy damaged, should be timely correction and replacement.
CONTACT DETAILS
Phone: +86 13816377866
Email: jimmy011@126.com
Add:NO999, Sunqiao RD, Pudong area, Shanghai, China
CONTACT US FOR FREE SAMPLE !
For more products related question ,Welcome to inquiry us .