Installation steps: 1) Pen off the bus roots within 15 mm of insulation on marking; ( 2) Screw straight busbar protection pipe lining, ensure the bus incoming busbar protection pipe lining; ( 3) Into the bus protection tube, in low temperature environment, needs a little push, when the bus protection pipe lining is introduced, show that installed correctly; ( 4) Take bus protection pipe lining and stored in plastic bags; ( 5) The green/yellow casing set into the shielded wire, does not need to heat shrinkable processing; ( 6) Pull back with tropical, above 25 mm; ( 7) Glass pressure sensitive adhesive tape, twisting three times; ( 8) Installation of terminal point and base, make the terminal whorl 25 higher than that of electric tracing band. 4 mm, and then screw down the screws; ( 9) The base fixed on the pipe with clamp, and the extra electric tracing band tape winding on the pipeline; ( 10) The bus between the conductive fiber cut open and peel, cut and remove the insulation of the middle separator, and the bus bar is clean; ( 11) Bus and shielding metal net, through the terminal, respectively connected to the power cord and the bottom line, lifted the lid and put the wires in the box pack.